How Many Smoke Alarms Do I Need in a QLD Home, and Where Do They Go?

Byron Knight, Director of Knight Electrical Solutions
Byron Knight, Licensed Electrical Contractor
QLD Lic. 1511406 · 20+ years’ experience · Gold Coast & SEQ · Updated November 2026

The 1 January 2027 deadline is now weeks away, and the most common question we get about it is how many alarms a home actually needs. Queensland law never gives a number. It gives a list of places an alarm must go, and the count falls out of your floor plan.

This guide walks through the required locations, how to count them for common Gold Coast layouts, the mounting rules that decide exactly where each alarm sits on the ceiling, the trouble spots near kitchens, bathrooms, fans and air conditioners, and when you need a licensed electrician.

Who has to comply, and by when

The Queensland Fire Department’s smoke alarms page says that by 1 January 2027 all existing private homes, townhouses, units and manufactured homes need interconnected photoelectric smoke alarms. The rules have been phasing in since 2017:

Date Who it applies to
1 January 2017 New homes and substantially renovated homes
1 January 2022 Homes being sold or leased (the QFD FAQ says this includes re-renting a home)
1 January 2027 All remaining homes, including owner-occupied houses and units

That timeline comes from the QFD’s smoke alarm reforms page, which also sets out what every alarm must be:

Where smoke alarms must go in a Queensland home

The locations are set by section 55C of the Building Fire Safety Regulation 2008. An alarm must be installed:

  1. In each bedroom. The QFD’s wording is “in each bedroom, or where you sleep”.
  2. In the hallway on each storey with bedrooms. If one or more bedrooms are connected by a door to a hallway, an alarm goes in that hallway.
  3. Between a bedroom and the rest of the home. If a bedroom isn’t connected by a door to a hallway, the alarm goes in the part of the storey between that bedroom and the rest of the dwelling.
  4. On every storey without bedrooms. At least one alarm goes on the most likely path of travel from anywhere on that storey to an exit outside.
Be wary of anyone who quotes a number before seeing your home. Queensland’s guide to buying smoke alarms gives “saying that you need more smoke alarms installed than the law says you do” as an example of false or misleading conduct by traders. The right number is whatever your layout needs to cover every required location.

How many smoke alarms do I need? Worked examples

Because the count follows the floor plan, the best way to answer is with examples. These are our worked readings of the rules above for typical Gold Coast layouts. Your home may differ, for example where bedrooms open onto living areas or there’s more than one hallway.

Home layout Typical minimum Where they go
2-bedroom unit, single level, both bedrooms off one hallway 3 Each bedroom, plus the hallway
3-bedroom lowset house, bedrooms off one hallway 4 Each bedroom, plus the hallway
4-bedroom house, three bedrooms off one hallway, main bedroom opening straight onto the living area 6 Each bedroom, the hallway, and between the main bedroom and the living area
2-storey townhouse, 3 bedrooms upstairs off a hallway, living downstairs 5 Each bedroom, the upstairs hallway, and one downstairs on the path to the exit
Highset house with a downstairs rumpus or granny flat Depends on use Upstairs as above. Downstairs, at least one on the path to the exit if no one sleeps there. If anyone sleeps downstairs, that room needs its own alarm plus one in the hallway or between it and the rest of the home. A self-contained granny flat needs its own set

All of them must be interconnected, so an alarm going off in the downstairs living room also sounds in the bedrooms. In our experience, plenty of Gold Coast homes have the right number of alarms in the right places but no interconnection, or a mix of brands that won’t talk to each other. In our experience, sorting that out is a big part of our smoke alarm installation work involves.

Exactly where each alarm sits: the mounting rules

Section 55C also sets where on the ceiling or wall an alarm can be mounted. In plain terms:

Situation Rule
Flat ceiling Mount on the ceiling where practicable, not within 300 mm of a corner where the ceiling meets a wall
Ceiling not practicable, exposed beams or joists On the underside of a beam or joist no deeper than 300 mm from the ceiling
Ceiling not practicable and no suitable beam or joist On a wall, between 100 mm and 300 mm below the ceiling, and more than 300 mm from the corner of two walls
Sloping ceiling Between 500 mm and 1,500 mm from the apex
Light fittings Not within 300 mm of a light fitting
Air conditioning and ceiling fans Not within 400 mm of an opening that supplies air from an air conditioner or forced-air ventilation, or of the blades of a ceiling fan
Stairwells Not where an obstruction stops rising smoke reaching the alarm

The QFD’s smoke alarm FAQ sums it up as on the ceiling, 300 mm from corners or lights and 400 mm from anything that may blow air. It also notes that the centre of the room is the preferred spot but not a requirement. In our experience, most Gold Coast bedrooms have a ceiling fan and many have a split system, so the 400 mm rule is the one that most often moves an alarm away from where people expect it.

Kitchens, bathrooms and false alarms

In our experience, an alarm that goes off every time someone makes toast ends up pulled down, which is the worst outcome. The 2016 smoke alarm amendments to Queensland’s fire services law allow for this. Where it’s impracticable to put an alarm in the required spot, an owner may put it somewhere else that still warns occupants. The example given is an alarm regularly set off by bathroom steam or kitchen fumes being moved to another appropriate location.

The QFD FAQ lists other causes of false alarms, including dirt, age, a faulty device and dirty power, and says hardwired alarms shouldn’t be wired to lighting circuits with dimmers. It also says to discuss hardwired alarms with a licensed electrician. Our post on why a smoke alarm keeps beeping covers the chirping side of the problem.

Don’t do this

Hardwired or battery: do I need an electrician?

It depends on what you have now. The QFD FAQ says 240-volt smoke alarms connect to the electricity supply and must be connected by a licensed electrician, while non-removable 10-year battery alarms don’t need an electrician. WorkSafe Queensland says the same about hardwired 240V alarms.

Where hardwired alarms are involved, we check the alarm circuit as part of a switchboard inspection, because in our experience an old alarm circuit without safety switch protection, or one on a dimmed lighting circuit, is a common find. Our smoke alarm compliance guide covers brand mixing, 9V backup batteries and what to check if you upgraded a few years ago.

Units, townhouses, rentals and granny flats

For the wider picture on rentals, see how often landlord electrical safety checks should happen. For who owns what in a unit block, see body corporate vs unit owner responsibilities.

Getting it done before 1 January 2027 on the Gold Coast

  1. Count your required locations. Walk the house with the four rules above and mark each bedroom, hallway and bedroom-free storey on a sketch.
  2. Check what you have. Look for the manufacture date and “photoelectric” on each alarm, and whether it’s hardwired or battery.
  3. Test interconnection. Press the test button on one alarm and listen for the others. If they don’t all sound, you’re not compliant.
  4. Book early. We’re fitting alarms across Palm Beach, Elanora, Burleigh Waters, Varsity Lakes, Robina and Currumbin Waters now, and in our experience bookings bunch up in the last weeks before a deadline.

The work runs through our smoke alarm installation service. Landlords and property managers can bundle it with a rental electrical safety check.

Frequently asked questions

How many smoke alarms do I need in Queensland?

The law doesn’t set a number. It requires an alarm in every bedroom, in the hallway connecting bedrooms to the rest of each storey, between a bedroom and the rest of the home where there’s no hallway, and at least one on any storey without bedrooms. A three-bedroom single-storey house with all bedrooms off one hallway needs four.

Do I need a smoke alarm in every bedroom in QLD?

Yes. Section 55C of the Building Fire Safety Regulation 2008 requires a smoke alarm in each bedroom. The Queensland Fire Department’s wording is “in each bedroom, or where you sleep”, so a room used for sleeping, such as a converted study or downstairs rumpus, should be treated as a bedroom.

Do I need a smoke alarm in the living room or kitchen?

Only if your layout requires it. On a storey with bedrooms, the required spots are bedrooms and the hallway or area between bedrooms and the rest of the home. On a storey without bedrooms, at least one alarm goes on the most likely path to an exit, which often passes through living areas. Avoid placing alarms right where cooking fumes collect.

How far from a ceiling fan or air conditioner must a smoke alarm be?

At least 400 mm. The regulation says a smoke alarm must not be within 400 mm of the blades of a ceiling fan or of an opening that supplies air from an air conditioner or forced-air ventilation. It also must not be within 300 mm of a light fitting or of the corner where the ceiling meets a wall.

Can I install smoke alarms myself in Queensland?

Only battery ones. The Queensland Fire Department says non-removable 10-year battery alarms can be installed without an electrician, but 240-volt alarms must be connected by a licensed electrician. If your home already has hardwired alarms, the replacements must also be hardwired, so a licensed electrician needs to do the job.

Do my smoke alarms all need to be interconnected?

Yes. Every alarm must be interconnected with every other alarm in the home, so that if one detects smoke they all go off. The Queensland Fire Department says interconnection can be wired, wireless or a combination, and wireless options exist for both 240-volt and battery alarms.

Does the 2027 smoke alarm deadline apply to units?

Yes. The Queensland Fire Department says the rules cover class 2 buildings, which are units and apartments, and that all existing units must comply by 1 January 2027. The law puts the duty on the owner of the dwelling, generally the lot owner, so check with your body corporate what detection is already installed before you buy alarms.

What happens if my home isn’t compliant by 1 January 2027?

The Queensland Fire Department says owners or landlords proven not to comply will receive an infringement notice. More importantly, interconnection means an alarm where a fire starts also sounds in the bedrooms, so people asleep are warned sooner. Getting your alarms compliant before the deadline avoids both problems.

Need your smoke alarms compliant before 1 January 2027? Call us. We’ll work out how many your layout needs and give you a fixed price on site.